Skip to product information
Dwyer EPC2LG

Dwyer EPC2LG | Analog to Pneumatic Output Transducer | 0 to 10 psi

Part Number : EPC2LG

The Dwyer EPC2LG is an analog to pneumatic output transducer: analog Input (0-5VDC), Pressure Output (0-10PSI), Dual Valve, Maintains Branch Pressure , High Flow, Gauge, (0-10V, 0-15V 0-20mA), (0-15PSI, 0-20PSI).

The ACI Series EPC functions as an electric-to-pneumatic transducer, converting analog input signals into proportional pneumatic outputs. These units modulate control valves to regulate branch line pressure according to a set point determined by the input signal. The series is designed for panel mounting with electrical terminals on one end and pneumatic connections on the other. The Series EPC operates within an ambient temperature range of 35 to 120°F (1.7 to 48.9°C) and a humidity rating of 10 to 95% non-condensing. Storage is supported from -20 to 150°F (-28.9 to 65.5°C).

  • Accuracy Detail: Output Pressure Accuracy: 1% room temperature
  • Air Consumption: 2300 SCIM
  • Air Supply Pressure, Max: 25 psi
  • Air Supply Pressure, Min: 22 psi
  • Approvals: RoHS2, WEEE
  • Auto/Manual function: Manual/Auto Override Switch: MAN funciton = output can be varied
Availability: in stock
For pricing, please contact our experts.