Part Number : 2813-WP

The Dwyer Instruments 2813-WP is a Series 2800 current-to-pressure (I/P) transducer that converts a 4-20 mA input signal into a 3-15 psig (0.2-1.0 bar) pneumatic output. It features a NEMA 4X (IP66) enclosure with CE, CSA and FM approvals for intrinsically safe applications.

Genuine Control Techniques stock · Free UAE-wide shipping

Part Number: 2813-WP

Request a quote in under a minute — call +971 6 5436933.

Product Overview

The Dwyer 2813-WP I/P transducer uses a closed-loop pressure feedback system to carefully control pneumatic output while compensating for fluctuations in supply pressure, temperature, mounting angle and vibration. This makes it suitable for demanding industrial installations, including applications where the transducer is field mounted directly on a valve.

A piezoceramic actuator with a protective covering provides a continuous barrier against impurities and humidity, supporting reliable operation in demanding environments. The Series 2800 design is field reversible and incorporates a NEMA 4X enclosure, with CSA and FM approvals for intrinsically safe applications.

The 2813-WP accepts a 4-20 mA loop-powered input and produces a proportional 3-15 psig (0.2-1.0 bar) pneumatic output. Its output capacity reaches 4.5 scfm at 25 psig supply and 12.0 scfm at 100 psig supply.

Installation is flexible, with input and output ports available on both the front and rear of the unit. The electrical connection is 1/2" female NPT, while the pressure connection is 1/4" female NPT. External zero and span adjustments allow the transducer to be calibrated in the field.

The housing is constructed from chromate-treated aluminum with epoxy paint and is rated for operation from -40 to 160°F (-40 to 71°C). With a compact weight of approximately 0.8 lb (0.37 kg), the 2813-WP is suitable for valve, panel and remote mounting applications where space and installation flexibility matter.

Key Benefits

  • Converts 4-20 mA electrical signals to 3-15 psig (0.2-1.0 bar) pneumatic output
  • Closed-loop pressure feedback compensates for supply, temperature, mounting-angle and vibration effects
  • Piezoceramic actuator with protective covering helps resist impurities and humidity
  • Suitable for field mounting on control valves
  • NEMA 4X (IP66) enclosure
  • CE, CSA and FM approvals
  • Intrinsically safe design
  • Front and rear input/output ports for flexible installation
  • External zero and span adjustments for field calibration
  • Loop-powered operation
  • Free UAE-wide shipping on genuine Dwyer stock

Who This Product Is Best For

The Dwyer 2813-WP is suited for process, HVAC and industrial control applications requiring an intrinsically safe current-to-pressure signal converter.

It is particularly useful for systems where a 4-20 mA electrical control signal must be converted into a 3-15 psig pneumatic signal for a valve positioner, actuator or other pneumatic final control element.

The compact Series 2800 construction also makes it suitable for field-mounted valve applications, panel installations and remote mounting, depending on the system configuration.

How to Specify & Commission It

  1. Confirm that the 3-15 psig (0.2-1.0 bar) output range matches the requirements of the final control element.
  2. Connect the 4-20 mA loop-powered input using the 1/2" female NPT electrical connection.
  3. Connect the air supply and pneumatic output through the 1/4" female NPT pressure connection.
  4. Ensure the air supply is at least 5 psig above the maximum required output and does not exceed 100 psig.
  5. Use the external zero and span adjustments to complete field calibration as required.

Frequently Asked Questions

What does the Dwyer 2813-WP do?

The 2813-WP converts a 4-20 mA current signal into a proportional 3-15 psig (0.2-1.0 bar) pneumatic output pressure.

What is the output range of the 2813-WP?

The transducer provides a 3-15 psig (0.2-1.0 bar) pneumatic output.

What safety approvals does the 2813-WP have?

The unit carries CE, CSA and FM approvals and uses a NEMA 4X (IP66) enclosure for applications requiring intrinsic-safety protection.

What connections does the 2813-WP use?

It uses a 1/2" female NPT electrical connection and a 1/4" female NPT pressure connection.

Is the Dwyer 2813-WP loop powered?

Yes. The 2813-WP uses a 4-20 mA loop-powered input.

Can the 2813-WP be calibrated in the field?

Yes. The unit provides external zero and span adjustments for field calibration.

What air supply does the 2813-WP require?

The minimum supply pressure is 5 psig (0.3 bar) above the maximum output pressure, while the maximum supply pressure is 100 psig (6.9 bar).

What is the operating temperature range?

The specified operating temperature range is -40 to 160°F (-40 to 71°C).

What is the difference between the 2813-WP and 2816-WP?

Both models use the same Series 2800 construction and approvals. The 2813-WP provides a 3-15 psig (0.2-1.0 bar) output, while the 2816-WP provides a 6-30 psig (0.4-2.1 bar) output.

Is genuine stock available with UAE shipping?

Yes. Genuine Dwyer stock with free UAE-wide shipping is available through General Tech Services LLC. Call +971 6 5436933 for pricing and current availability.

Request a Quote Today

For pricing, availability or technical assistance with the Dwyer 2813-WP I/P transducer, contact General Tech Services LLC.

Call: +971 6 5436933
Website: www.generaltechshop.ae

 

Availability: low stock
Free UAE shipping available
For pricing, please contact our experts.