Dwyer PXP100 | Analog to Pneumatic Output Transducer | 0 to 100 psi
The Dwyer PXP100 is an analog to pneumatic output transducer: analog Input (0-5VDC), Pressure Output (0-100PSI), Dual Valve, Maintains Branch Pressure, (0-10V, 0-15V, 0-20mA Selectable).
The ACI Series PXP100 is an analog to pneumatic output transducer designed to convert an analog electrical input signal into a proportional pneumatic pressure output. The unit automatically modulates its control valves to regulate branch line pressure to a selected set point determined by the input signal, providing a 0 to 100 psig (0-689.5 kPa) modulating output. The PXP100 operates within an ambient temperature range of 35 to 120°F (1.7 to 48.9°C) and a humidity rating of 10 to 95% non-condensing. Storage is supported from -20 to 150°F (-28.9 to 65.5°C).
- Accuracy Detail: Output Pressure Accuracy: 1% full scale @ room temperature
- Air Consumption: 2300 SCIM
- Air Supply Pressure, Max: 106 psi
- Air Supply Pressure, Min: 102 psi
- Approvals: RoHS2, WEEE
- Auto/Manual function: Manual / Auto Override: MAN function = output can be varied
Other models in this series
Click a row to open that product.
Highlighted values differ from the model you are viewing.