Dwyer Instruments IP-43 | Current to pressure transducer | 4-20 mA input | 3-27 psi (20-185 kPa) output
An input signal of current is converted to a linearly proportionate pneumatic output pressure by the Model IP-43 Current to Pressure Transducers. Integrated volume booster, minimal air usage, field reversible output (which yields an output inversely proportional to the input signal), and adjustable zero and span are among the features. Both exterior installation and splashdown are permitted by the robust NEMA 4X enclosure. Applications requiring the functioning of pneumatic valve positioners, damper and louver actuators, air cylinders, web tensioners, clutches, brakes, and final control elements can use this IP.

Free UAE shipping available
- Specifications
- Features
- Downloads
Air Consumption | 0.03 SCFM (0.5 m3/h) typical |
Air Pressure | Minimum: 3 psig (21 kPa) above maximum output; Maximum: 100 psig (700 kPa) |
Approvals | CE, FM |
Connection | Electrical: 1/2" female NPT |
Connection | Pressure: 1/4" female NPT |
Hysteresis | <1% of span |
Input Impedance | 220 ohms |
Input signal | 4-20 mA |
Linearity | <+/-0.75% of span |
Maximum operating temperature | -20 to 140°F (-30 to 60°C) |
Output | 3-27 psi (20-185 kPa) |
Output | Capacity: 4.5 SCFM (7.6 m3/h ANR) at 25 psig (175 kPa) supply; 12 SCFM (20 m3/h) at 100 psig (700 kPa) supply |
Power | Loop powered |
Relief Capacity | 2 SCFM (3.4 m3/h) at 5 psig (35 kPa) above 20 psig (140 kPa) setpoint |
Repeatability | <0.5% of span |
Sensitivity | Supply Pressure: <+/-0.1% of span per psig (<+/-0.15% of span per 10 kPa) |
Weight | 2.1 lb (0.94 kg) |
- Loudness booster integrated in.
- Minimal use of air.
- Adaptable zero plus span settings.
- NEMA 4X protective housing.
- Reversible field.
Related Products

Dwyer Instruments IP-44 | Current to pressure transducer | 4-20 mA input | 6-30 psi (40-200 kPa) output

Dwyer Instruments IP-44 | Current to pressure transducer | 4-20 mA input | 6-30 psi (40-200 kPa) output

Dwyer Instruments IP-42 | Current to pressure transducer | 4-20 mA input | 3-15 psi (20-100 kPa) output

Dwyer Instruments IP-42 | Current to pressure transducer | 4-20 mA input | 3-15 psi (20-100 kPa) output

Dwyer Instruments 2816-WP | Current to pressure transducer | 4-20 mA input | 6-30 psig (0.4-2.1 bar) output

Dwyer Instruments 2816-WP | Current to pressure transducer | 4-20 mA input | 6-30 psig (0.4-2.1 bar) output

Dwyer Instruments 2813-WP | Current to pressure transducer | 4-20 mA input | 3-15 psig (0.2-1.0 bar) output

Dwyer Instruments 2813-WP | Current to pressure transducer | 4-20 mA input | 3-15 psig (0.2-1.0 bar) output

Dwyer Instruments 2716-WP | Current to pressure transducer | 4-20 mA input | 6-30 psig (0.4-2.1 bar) output

Dwyer Instruments 2716-WP | Current to pressure transducer | 4-20 mA input | 6-30 psig (0.4-2.1 bar) output

Dwyer Instruments 2916-E | Current to pressure transducer | 4-20 mA input | 6-30 psig (0.4-2.1 bar) output

Dwyer Instruments 2916-E | Current to pressure transducer | 4-20 mA input | 6-30 psig (0.4-2.1 bar) output

Dwyer Instruments 2913-E | Current to pressure transducer | 4-20 mA input | 3-15 psig (0.2-1.0 bar) output

Dwyer Instruments 2913-E | Current to pressure transducer | 4-20 mA input | 3-15 psig (0.2-1.0 bar) output