Skip to product information
HIM Smart HART Loop Interface and Monitor | With Integral Display - generaltechuae

Moore Industries HIM/HART/3AO/24DC/-2PRG-RF [DIN] | HIM Smart HART Loop Interface and Monitor | HART Input, 3 Analog Outputs, 2 Alarm Relays, Integral Display

Part Number : HIM/HART/3AO/24DC/-2PRG-RF [DIN]

The Moore Industries HIM reads the digital data from a smart HART transmitter or valve positioner and breaks it out into up to three isolated, scalable analog outputs, with no extra process penetrations or wiring. This model has three analog outputs (3AO), two programmable alarm relays (-2PRG) and enhanced RFI/EMI protection (-RF), runs from 24 Vdc, and has a 5-digit display.

Key features

  • Three programmable 0-20 mA / 4-20 mA outputs tracking the primary, second, third or fourth HART variable or valve parameters
  • Two relays configurable for high/low process alarms or HART/loop diagnostic faults
  • Configurable as HART primary or secondary master, or in passive listen mode
  • Works with normal (poll/response) and burst HART modes
  • Large 5-digit display of a selected variable in engineering units
  • Output accuracy 0.015% of maximum span; outputs isolated to 500 Vrms
  • DIN-rail or surface mounting; operating temperature -40 to +85 C